Simulateur digital des
convertisseurs de puissance à thyristors
Par V. Rajagopalan, A. Lescarbeau
et J. Pelletier, Université du Québec à Trois-Rivières,
K. Sankara Rao, Concordia
University, et D. Mukhedkar, École Polytechnique
Pages: 5-10
This paper deals with a digital simulator for the analysis of any
thyristor converter. The analysis is based upon a topological method of
formulation of state equations and power thyristors and diodes are modelled as
inductances. The value of each thyristor inductance changes from a finite value
equal to the di/dt limiting series inductance, while conducting, to an infinite
value when blocked. The simulator takes into consideration the presence of the
snubber circuits associated with each thyristor element. The simulalor library
which has been named ATOSEC I has been developed having in mind the creation of
a tool for the design by computer aided analysis of power electronic
converters. It has been presently implemented on a CDC CYBER and will be
available to prospective users from the authors.
Le développement des circuits convertisseurs à thyristors durant les deux
dernières décades a créé un besoin urgent d¹un simulateur des convertisseurs
électroniques de puissance afin de faciliter leur conception par l¹analyse
aidée de l¹ordinateur. Le Logiciel ATOSEC I qui a été développé dans ce but
peut amener à la conception rapide et efficace de ces convertisseurs sans
obliger la construction d¹un prototype très coûteux au départ. Nous avons
illustré, moyennant un exemple du démarrage d¹un pont convertisseur à
thyristors, l¹application du logiciel ATOSEC I pour l¹analyse d¹un pont
redresseur. Le Logiciel ATOSEC I ainsi que les manuels de l¹utilisateur sont
disponibles et peuvent être obtenus en écrivant aux auteurs.
A comparison of
the maximum entropy method and the periodogram method applied to the spectral
analysis of computer-simulated radar clutter
By S. B. Kesler and
S. Haykin, Communications Research Laboratory, McMaster University
Pages: 11-16
The maximum entropy method (MEM) for spectral analysis is described and
compared to Welch¹s procedure using the fast Fourier transform (FFT) algorithm.
Comparative results are presented for the application of these two spectral
analysis techniques to computer-generated radar clutter data produced using a
model developed by Hawkes and Haykin. These results show that the resolution
capabilities of the MEM are superior to Welch¹s procedure. This feature is
particularly notable in the analysis of very short clutter data records.
La méthode entropique maximale (MEM) pour l¹analyse spectrale est décrite et
comparée à la méthode Welch utilisant l¹algorithme Fourier à transformation
rapide (FFT). Des résultats comparatifs sont présentés pour l¹application de
ces deux techniques d¹analyse spectrale à des signaux parasites engendrés par
ordinateur, à l¹aide d¹un modèle mis au point par Hawkes et Haykin. Ces
résultats montrent que les capacités de résolution du MEM sont supérieures à la
méthode Welch. Cette caractéristique est particulièrement remarquable dans
l¹analyse des signaux parasites en petites quantités.
Ground
controlled conversion of Communications Technology Satellite (CTS) from spinning
mode to three-axis stabilized mode
By D. A. Bassett, SED
Systems
Ltd., Saskatoon
Pages: 17-26
The Communications Technology Satellite was launched on Jan. 17, 1976
and became operational on Feb. 2. The maneuvres and operations performed to
convert the spacecraft from its initial spinning mode to its on-station,
three-axis mode are referred to as Attitude Acquisition.
During this phase, the maneuver and attitude control actions required were
determined by ground based data processing and conducted via ground command.
The ground based system is described, with emphasis on the attitude control
software; its concept, implementation, development, verification and flight
performance. Experience confirms that this technique provides a flexible
alternative to on-board hardware for a geo-synchronous satellite.
Le Satellite Technologique de Communications a été lancé le 17 janvier 1976
et est devenu opérationnel le 2 février. Les manoeuvres et
opérations exécutées pour convertir le vaisseau spatial de son mode initial de
rotation au mode sur station à trois axes, constituent ce qu¹on appelle
l¹acquisition de l¹attitude. Au cours de cette phase, les manoeuvres et les
mouvements de contrôle d¹attitude requis ont été déterminés par traitement des
données au sol, et transmis par commande au sol. Le système basé au sol est
décrit, en insistant sur les programmes de contrôle d¹altitude, leur concept,
exécution, développement, vérification et les résultats en vol. L¹expérience
confirme que cette technique donne une alternative flexible au matériel à bord
pour un satellite géo-synchrone.
Optimal and
conventional array processing
By S. Pasupathy, Department
of Electrical Engineering, University of Toronto.
Pages: 27-31
Optimal and conventional (beamform-square-integrate) detectors using a
linear array are compared to identify those noise fields for which the optimal
spatial processor performs significantly better than the conventional detector.
Conditions are also derived under which the conventional processor performs
nearly optimally. Particular noise fields are identified as good or bad candidates
for the use of optimal techniques by the use of a set of simple criteria stated
in terms of parameters such as noise power, noise spatial spectral bandwidth,
array beamwidth, etc.
Les détecteurs optimaux et conventionnels (en faisceaux-carrés-intégrés)
utilisant un réseau linéaire, sont comparés pour l¹identification des champs de
bruit pour lesquels l¹unité de traitement spatiale optimale donne des résultats
sensiblement meilleurs que ceux des détecteurs conventionnels. On a également
dérivé des conditions dans lesquelles l¹unité de traitement conventionnelle
fonctionne de manière presque optimale. Les champs de bruit particuliers sont
identifiés en tant que bons ou mauvais candidats à l¹utilisation des techniques
optimales, par l¹emploi d¹un ensemble de critères simples énoncés sous forme de
paramètres, tels que puissance de bruit, largeur de bande spectrale et spatiale
du bruit, largeur de bande des faisceaux, etc.
An analog power
system simulator
By J. Carr, Carr
Consulting, Kitchener, Ontario*
Pages:32-36
The general requirements for power system simulation are outlined and
the characteristics and uses of existing simulators described. The theoretical
operation of an active analog electronic circuit known as an impedance
converter is introduced and its use in a novel power system simulator
described. Results are given to demonstrate the performance of this real-time
phase-based modular simulator.
Les conditions générales de la simulation des systèmes d¹énergie sont
soulignées, et l¹on décrit les caractéristiques et les utilisations des
simulateurs existants. Le fonctionnement théorique d¹un circuit électronique
analogue actif, appelé convertisseur d¹impédance, est présenté, et l¹on décrit
son utilisation dans un nouveau simulateur de système d¹énergie. Les résultats
sont donnés pour démontrer la performance de ce simulateur modulaire à phase en
temps réel.
Les effets du champ
électrostatique et leur influence sur le travail du personnel d¹entretien dans
les postes des monteurs des lignes haute tension
Par M. De Vizio et R. Duquette, Hydro-Québec,
Montréal, et N. Giao Trinh, Institut de Recherche de I'Hydro-Québec, Varennes,
Québec.
Pages: 37-40
Cet article résume les résultats d'une étude relative aux effets du champ
électrostatique et à leur répercussion sur le travail du personnel d¹entretien
des postes et celui des monteurs des lignes H.T. Généralement, les effets du
champ électrostatique se manifestent soit sous la forme d¹un courant de régime
induit dans la personne, soit sous la forme d¹impulsions de courant de très
courte durée. À l¹occasion des travaux exécutés dans les postes et sur les
lignes H.T., le courant de régime permanent induit dans la personne atteint
rarement le seuil de sécurité 5 mA. Les impulsions de courant, par contre,
peuvent atteindre des niveaux de charge de quelques microcoulombs et incommoder
les ouvriers. Des essais ont été réalisés à l¹Hydro-Québec pour évaluer
l¹efficacité des vêtements conducteurs, des bottines conductrices et autres
moyens de protection contre les effets du champ électrostatique. Les résultats sont
présentés dans ce rapport.
This article summarizes the results of a study on the effects of the
electrostatic field and their repercussions on the work of station maintenance
personnel and H.T. line riggers. In general the effects of the electrostatic
field are felt either in the form of steady state a.c, current induced in the
body, or in the form of very short surges of current. During work performed in
stations and on H.T. lines, the steady state a.c. current induced in the body
rarely goes as high as the safety margin of 5 mA. Current surges, however, can
reach charge levels of several microcoulombs and inconvenience workers. Tests
have been performed at Hydro-Québec to evaluate the efficiency of conductive
clothing, conductive boots and other means of protection against the effects of
the electrostatic field. The results are presented in this report.
1978
– Volume 3 – Numéro 2
The Canadian high speed
magnetically levitated vehicle system
By D, L. Atherton, Physics
Department, Queen's University;
P. R. Belanger, Department
of Electrical Engineering, McGill University;
P. E. Burke, Department of
Electrical Engineering, University of Toronto;
G. E. Dawson Department of
Electrical Engineering, Queen's University;
A. A. Eastharn, Canadian
Institute of Guided Ground Transport, Queen's University;
VV. F. Hayes, Division of
Mechanical Engineering National Research Council;
B. T. Ooi, Department of
Electrical Engineering, McGill University;
P. Silvester, Department of
Electrical Engineering, McGill University;
G . R. Slernon Department
of Electrical Engineering . University of Toronto.
Pages: 3-26
A
technically feasible high speed (400-480 km/h) guided ground transportation
system, based on the use of the vehicle-borne superconducting magnets for
electrodynamic suspension and guidance and for linear synchronous motor
propulsion, has been defined as a future modal option for Canadian application.
A variety of sophisticated analytical techniques have been developed to
establish a comprehensive theoretical base for conceptual design studies.
Analysis and design proposals have been validated by large-scale tests on a
rotating wheel facility and by modeling system components and their
interactions.
Thirty
tonne vehicles carrying 100 passengers operate over a flat-topped elevated
guideway, which minimizes system down-time due to ice and snow accumulation and
facilitates the design of turn-outs. A clearance of up to 15 cm is produced by
the electrodynamic interaction between the vehicle-borne superconducting
magnets and aluminum guideway strips.
Propulsion
and automatic system control is provided by the superconducting linear
synchronous motor which operates at good efficiency (0.74) and high power
factor (0.95). The vehicle is guided primarily by the interaction between the
LSM field magnet array and flat null-flux loops overlying the stator windings
in the guideway.
The
linear synchronous motor, electrodynamic suspension as well as levitation strip
Joints, parasitic LSM winding losses and limitations to the use of
ferromagnetic guideway reinforcement, have been investigated experimentally on
the lest wheel facility.
Careful
consideration has been given to shielding the vehicle passenger compartment
from stray fields exceeding 20 mT.
Isochoric
(sealed) dewars, rather than on-board closed cycle refrigeration, are proposed
for a potentially lightweight reliable cryogenic support system. Conceptual
design studies indicate the attractive features of this mode of operation, but
detailed design and fabrication of tubular test dewars are necessary to
demonstrate its operational feasibility.
The
use of a secondary suspension assures adequate dynamic stability, and good ride
quality is achieved by optimized passive components with respect to lateral
modes and by an actively controlled secondary suspension with respect to
vertical motion.
It
is concluded that the proposed Maglev system is a sufficiently promising
approach to high speed guided ground transport to warrant an assessment of its
economic viability in Canada, the development of critical components
(particularly lightweight superconducting magnets), and continued technical
refinement.
Un système
de transport terrestre guidé à vitesse élevée (400-480km/h) techniquement
réalisable et ayant recours à l¹usage d¹aimants supraconducteurs de
substentation pour la suspension électrodynamique, la commande et la propulsion
du moteur synchrone linéaire, a été proposé comme option modale pour de futures
applications canadiennes. On a rassemblé un éventail de techniques analytiques
pour définir une base théorique générale aux fins d¹études conceptuelles. Les
essais à grande échelle sur un appareil de simulation rotatif, ainsi que
l¹étude en modèles des éléments du système et de leur relation ont confirmé les
plans de conception et les analyses.
Des
véhicules de trente tonnes peuvent transporter 100 passagers sur une rampe
surélevée plate, minimisant ainsi les ralentissements du système causés par
l¹accumulation de la neige ou de la glace et facilitant la conception des
courbes. Le contact électrodynamique entre les aimants supraconducteurs de
substentation et les baguettes de la rampe en aluminium créent un espace libre
allant jusqu¹à 15cm.
Un moteur
synchrone linéaire supraconducteur à bon rendement (0,74) et à facteur de
puissance élevée (0,95) constitue le système de propulsion et de commande
automatique. La commande fondamentale au véhicule s¹effectue par l¹interaction
entre le réseau du champ magnétique du moteur synchrone linéaire elles boucles
plates isolées recouvrant les bobinages du stator dans la rampe.
On a étudié
expérimentalement le moteur synchrone linéaire. la suspension électrodynamique
ainsi que les joints de la bande de substentation, les limites et les pertes
parasites de l¹enroulement de moteur synchrone linéaire avec l¹armature de la
rampe ferromagnétique.
On a
particulièrement soigné le blindage du compartiment des voyageurs pour éviter
les champs vagabonds supérieurs à 20 mT.
Des Dewars
(scellés) isocronotiques plutôt qu¹un système de réfrigération en circuit fermé
sur plaque, sont proposés comme option pour le système de support cryogénique
léger et fiable. Les études de configuration conceptuelles soulignent les
caractéristiques avantageuses de ce mode de fonctionnement, mais les plans
détaillés et la fabrication de Dewars d¹essais tubulaires sont nécessaires pour
en démontrer la praticabilité opérationnelle.
L¹usage
d¹une suspension secondaire assure une stabilité dynamique adéquate.
L¹optimisation des éléments passifs par rapport aux modes latéraux, et une
suspension secondaire sous contrôle actif par rapport au mouvement vertical
offrent un transport de bonne qualité.
Nous en
avons conclu que le système Maglev proposé s¹avère une option suffisamment
pleine d¹avenir comme mode de transport terrestre guidé à vitesse élevée pour
justifier une étude de sa rentabilité au Canada, de la production des éléments
principaux (en particulier les aimants supraconducteurs légers) elle
perfectionnement technique du système.
Prévention par chauffage de la
formation de givre ou de verglas sur les conducteurs cylindriques ou toronnés
Par P. McCornber, D. D. Nguyen et
J. Druez, Département des Sciences Appliquées, Université du Québec à
Chicoutimi.
Pages: 27-3
La puissance de chauffage par effet Joule nécessaire pour prévenir la
formation de givre ou de verglas sur un conducteur lisse ou toronné a été
étudiée. Des essais ont été effectués en soufflerie pour déterminer cette
puissance suivant différentes conditions de vitesse de température et de teneur
en eau de l'écoulement Ces essais montrent que la puissance nécessaire à la
prévention du givre augmente avec la présence de torons à la surface du
conducteur. Aux vitesses de vent ou se forme le givre, cet effet des torons est
dû en grande partie à l'augmentation de surface extérieure que la forme
circulaire des torons entraîne. Cet effet peut être diminué en utilisant un
conducteur ayant sur sa couche extérieure des torons trapézoïdaux. . Pour un
conducteur à surface lisse, sans torons, il est montré que la quantité de
chaleur nécessaire pour empêcher la formation de glace, est fonction de la
température, de la vitesse de l¹écoulement, de la teneur en eau, mais aussi du
coefficient de captation des gouttelettes par le conducteur.
The power required to prevent rime and glaze formation by Joule healing
on a smooth or stranded conductor was investigated. Experiments were conducted
in a wind tunnel to determine the effect of wind velocity, temperature and
water content on this power. Results show that the minimum power for ice
prevention increases for a stranded conductor At wind velocities at which rime
is formed on a conductor, the effect of the conductor strands is due mostly to
an increase in the heat transfer area and can be diminished by using a
trapezoidal cross-section stranded conductor. For a smooth cylindrical
conductor it is shown that the ice prevention power is a function of ambient
temperature, air stream velocity, water content, and droplet collection
efficiency of the conductor.
Digital data processing
applied to HF DF by phase measurement
By D. B. Miron, Hermes
Electronics Ltd., Dartmouth, Nova Scotia.
Pages: 34-38
This
paper presents sonic numerical methods for extracting wave direction from
sensor phase measurements. A single ring circular array is considered. Some
discussion of optimality is given. RMS error due to measurement noise is
derived. A simulation program is described and some results of its exercise are
given. Finally, some thoughts on implementation and future work are presented.
Ce papier pressente
des méthodes numériques pour extraire la direction de vague avec des mesures de
phase d¹un récepteur. Une formation circulaire est considérée. Une discussion
sur l'optimum est décrite avec une dérivation d¹erreur R.M.S. due à des mesures
de bruit. Un programme de simulation est décrit et des résultats de son usage
sont donnés. Finalement, quelques idées sur l¹exécution et le travail futur
sont décrites.
Time ratio control (TRC)
scheme for a dc series motor
Part I: performance
By P. C. Sen, Department of
Electrical Engineering, Queen's University, and
S. A. Doradla. Department of
Electrical Engineering, IIT, Kanpur, India
Pages: 39-43
This
paper is concerned with the detailed study of time-ratio-control (TRC) scheme
for a solid state dc series motor drive. The performance characteristics such
as torque-speed, supply power factor, supply harmonic content, peak armature
current variations are obtained and compared with those obtainable with the
commonly used phase angle control (PAC) scheme under identical operating
conditions. The comparative study has revealed that certain performances are
improved in the TRC scheme. The drive systems with PAC and TRC schemes are
simulated on a digital computer and an efficient time-saving method is employed
for computation. Oscillograms obtained from the experimental setup using a 3 HP
dc series motor are presented to demonstrate the feasibility of the schemes and
to verify the basic principles of operation
Cet article
traite de l¹étude détaillée d¹un projet de contrôle de rendement horaire (CRU)
pour un entraînement moteur à semi-conducteurs en série CC. Les
caractéristiques de rendement telles que le rapport moment de torsion/vitesse,
le coefficient de puissance d'alimentation, la teneur harmonique
d¹alimentation, et les fluctuations de pointe du courant d¹induit, sont
recueillies et comparées à celles obtenables avec le système communément
utilisé de contrôle d¹angle de phase (CAP), dans des conditions de
fonctionnement identiques. Cette comparaison montre que certaines performances
sont meilleures dans le système CRU. Les systèmes d¹entraînement à CAP et à CRH
sont simulés sur ordinateur et une méthode efficace et économique est employée
pour le calcul. Des oscillogrammes obtenus dans l¹expérience avec un moteur en
série CC de 3 CV, sont présentés pour illustrer la praticabilité des systèmes
et pour vérifier les principes fondamentaux de I l'opération.
Time ratio control (TRC)
scheme for a dc series motor
Part II:
commutation circuit analysis
By S. R. Doradla, Department
of Electrical Engineering, lIT,
Kanpur, India, and
P. C. Sen, Department of
Electrical Engineering, Queen's University.
Pages: 44-48
In
part I the chopper with time-ratio-control scheme has been considered as an
ideal switch and the effects of commutation circuit have been neglected. In
this part the chopper circuit is analyzed in detail by a modern technique. The
effects of the commutation circuit parameters on the successful operation of
the circuit and on the torque-speed characteristics are investigated. Experimental results are in agreement with
the theoretical results.
Dans la
première partie, l'interrupteur rotatif avec système de contrôle de rendement
horaire a été considére comme interrupteur idéal et les effets du circuit de
commutation ont été négligés. Dans cette partie, le circuit de l'interrupteur
rotatif est analysé en détail par une technique moderne. Les effets des
paramètres du circuit de commutation sur le fonctionnement efficace du circuit
et sur les caractéristiques du rapport moment de torsion/vitesse sont examinés.
Les résultats
expérimentaux coïncident avec les résultats théoriques.
1978
– Volume 3 – Numéro 3
Developments in magnetic
bubble memories
By E. Della Torre, Department
of Electrical Engineering, McMaster University, and
W. Kinsner, Department of
Electrical Engineering, University of Manitoba.
Pages: 3-9
This
paper presents two new developments for magnetic bubble memories, a bubble
propagate circuit and a bubble detector. The propagate circuit uses a channel
with periodic traps coupled with asymmetrically placed bars of soft magnetic
material to propagate bubbles undirectionally with an alternating transverse
magnetic field. This structure lends itself to very compact corners and
transfer gates used in bubble memories with operating margins virtually
identical to those of the straight line propagate circuit. A major-minor loop
memory structure based on the channel-bar propagator is discussed. The
structure yields independent propagation in the assembly and the storage loops
using two mutually perpendicular transverse magnetic fields. The active bubble
detector designed to match the excellent properties of the above circuit and to
provide a means of nondestructive read-out is also discussed. The detector is
based on a magneto-elastic phenomenon and does not require any electric current
to operate.
Ce texte
présente deux nouveaux développements dans le domaine des mémoires à bulles
magnétiques, un circuit de propagation à bulles et un détecteur de bulles. Le
circuit à propagation utilise un canal à trappes périodiques couplées à des
barres de matériel magnétique mou placées asymétriquement pour propager des
bulles unidirectionellement avec un champ magnétique longitudinal alternatif.
Cette structure se prête à des arêtes et des portes de transfert très denses
utilisées dans les mémoires à bulles, avec des marges d¹opération virtuellement
identiques à celles du circuit de propagation rectiligne. On y analyse une
structure majeure-mineure de mémoire à circuit bouclé basée sur le propagateur à
barre-canal. La structure produit une propagation indépendante dans les
circuits bouclés d¹assemblage et de mémoire, utilisant deux champs magnétiques
longitudinaux mutuellement perpendiculaires. On y analyse également le
détecteur de bulles actives conçu pour égaler les excellentes propriétés du
circuit ci-dessus, et pour fournir une méthode de lecture non destructive. Le
détecteur fonctionne sur la base d¹un phénomène magnéto-élastique et ne
requiert donc pas de courant électrique.
A novel equidistant pulse
control scheme for thyristor converters
By P. C. Sen MIEEE,
Department of
Electrical Engineering, , Queen's University,
M. L. MacDonald, MIEEE,
Powertronic Equipment Ltd., Scarborough, Ontario, and
D. J. Clarke, Department of
Electrical Engineering, Queen¹s University.
Pages: 10-14
Various
firing control systems for phase-controlled thyristor converters can be divided
into two groups: Individual phase control scheme and Equidistant pulse control
scheme. The basic principles, advantages and disadvantages of the two groups
are discussed in this paper. A novel equidistant pulse control scheme, simple
and economic, is evolved which tends to combine most of the good features of
the presently available firing control systems. Two types of this new control
scheme are described and tested experimentally. Their relative advantages and disadvantages are
discussed.
On peut
classer en deux groupes les différents systèmes de contrôle d¹allumage des
convertisseurs à thyristor à phase contrôlée: le schéma de contrôle de phase
individuelle, et le schéma de contrôle d¹impulsions équidistantes. Ce texte
analyse aussi les principes de base, les avantages et les inconvénients de
chacun des deux groupes. On y développe un nouveau schéma de contrôle d¹impulsions
équidistantes, simple et économique, qui vise à combiner la plupart des bonnes
caractéristiques des systèmes de contrôle d¹allumage actuellement disponibles.
On y expérimente et analyse deux types de nouveaux schémas de contrôle. Leurs
avantages et inconvénients relatifs sont également présentés.
A study of the
leakage current
of H.V. insulators under glaze and rime
By Masonori Hara* and C. Luan
Phan, IEEE Senior Member
Applied Science Department,
University of Quebec, Chicoutimi, Qué.
Pages: 15-22
Electrical
behavior of iced insulators was investigated by measurement of leakage current
and observation of growth and melting of icicles during icing periods. A long
rod elastomer insulator or a cap-and-pin porcelain insulator was suspended in a
cold room and supercooled droplets directed on them. The leakage current was
found to be made of four components: basic leakage current IB
melting current white arc current IW and flashover current IF.
IM and IW increased with applied voltage. With
glaze icing, an equilibrium was found between melting rate and icing rate, and
basic leakage current IB was proportional to the icing rate. At low
thickness of ice accumulation there was no white arc occurrence at temperature
near 0°C. Elsewhere, white arc threshold current was found to be independent of
icing regions and equal to about 18 mA rms. Hard rime icing was the most
dangerous icing type for H.V. insulators due to the high probability of white
arc occurrence.
Le
comportement des isolateurs sous H.T. pendant la formation du givre et du
verglas a été étudié en prenant le courant de fuite comme paramètre. Les
résultats montrent que le courant de fuite comprend quatre composantes appelées
respectivement courant (de fuite) de base, courant de fonte, courant d¹arc
blanc et courant d¹arc de contournement. En présence du verglas, il y a
équilibre entre le taux d¹accumulation de la glace et le taux de fonte,
l¹amplitude du courant de base est proportionnelle au taux d¹accumulation de
glace. Aux températures proches du point de congélation et pour de faibles
épaisseurs d¹accumulation, il n¹y a pas d¹arc blanc. Aux autres températures
les arcs blancs apparaissent lorsqu¹un seuil de 18 mA est atteint. Ce courant
seuil est indépendant du type de glace et du type d¹isolateur. Le givre lourd
est dangereux car les arcs blancs se produisent souvent avec ce type de glace.
Critères de cabiage et filerie
dans les postes et centrales
Par A. Valladolid, Projets
électrotechniques, Hydro-Québec, Montréal.
Pages: 23-26
Cette étude commence par faire une brève synthèse des connaissances
acquises quant à la nature des perturbations électriques, leur façon de
s¹introduire dans les circuits de commande, de mesure et de protection des
postes et centrales ainsi que les moyens d¹y remédier.
Elle tente ensuite de dissiper certains malentendus, à propos des câbles
blindés, pour ouvrir finalement la voie à des recommandations qui permettront à
l¹Hydro-Quéhec d¹obtenir une meilleure protection des équipements terminaux,
des câbles et de sou personnel.
This paper opens with a brief summary of accumulated knowledge with
respect to the nature of electrical disturbances, and their mode of penetration
into control, measurement and protection circuits of posts and generating
stations, together with means of remedying the situation.
It goes on to set aside certain misunderstandings concerning armoured
cables, to conclude by opening the way for recommendations which will enable
Hydro-Québec to obtain better protection for its terminal equipment, cables and
personnel.
Noise measurements on
telephone connections in Canada
By B. A. Black, MIEEE,
Department of¹ Electrical and Computer Engineering,
Clarkson College of
Technology, Potsdam, N.Y. and
P. H. Wittke, MIEEE, MCSEE,
Department of Electrical Engineering, Queen¹s University
Pages: 27-31.
User-oriented
results are presented of noise measurements made on a number of toll telephone
circuits within, and terminating in, Canada. Signal-to-noise ratios are given
along with tables showing the fraction of noise samples exceeding given values
and the fraction of calls having a noise sample exceeding given values, The
data were recorded in digital form on tape to preserve maximum dynamic range
and measurement bandwidth. It is anticipated that these results will provide
the designer of high-speed voiceband data transmission equipment with insight
into the environment in which his equipment must operate.
Ce texte
présente d¹une façon aisément utilisable les résultats des mesures de bruit
faites sur un certain nombre de lignes téléphoniques interurbaines, dont les
points de transmission et de réception sont situés au Canada. On y trouvera les
rapports signal/bruit, accompagnés de tables montrant la fraction des
échantillons de bruit qui dépasse une valeur donnée ainsi que la fraction des
appels dont l¹échantillon de bruit dépasse une valeur donnée. Les messages étaient
enregistrés sur ruban sous forme numérique pour conserver la gamme dynamique
maximale et la largeur optimale de bande de mesure. On espère que ces résultats
fourniront au concepteur d¹équipement de transmission à haute vitesse de
données à bande vocale, une meilleure compréhension du milieu dans lequel son
équipement doit fonctionner.
Bit timing transmission and
spectral shaping of digital signals
By K. Feher, MIEEE, MCSEE.
Department of Electrical Engineering, University of Ottawa,
and consultant, SPAR Technology.
Pages: 32-34
For
bit timing or bit synchronization of NRZ and multi-level random data,
conventional non-linear processing of the signal is usually performed at the
receiver. The performance of the synchronizer depends on the received
signal-to-noise ratio; obvisouly, non-linear processing does not enhance this
ratio. This paper presents a novel method for bit timing transmission, in which
the non-linear processing is performed at the transmitter. The transmitted
signal then becomes a modified NRZ or multi-level signal, having asymmetric and
finite rise and fall times and faster spectral roll-off than conventional NRZ
signals. The received signal can then be processed by linear methods to recover
the timing data.
Le
traitement en différé du signal est généralement fait au récepteur pour le
chronométrage et la synchronisation binaires de données aléatoires multiniveau
et NRZ. Le rendement du synchronisateur dépend du taux signal reçu/bruit; de
toute évidence, un traitement non linéaire n¹augmente pas ce taux. Ce texte présente
une méthode nouvelle pour la transmission à chronométrage binaire, dans
laquelle le traitement non linéaire est fait au transmetteur. Le signal
transmis devient alors un signal NRZ modifié ou un signal multiniveau avec des
temps de montée et de descente finis et asymétriques et ayant un transfert
spectral plus rapide que des signaux NRZ conventionnels. Le signal reçu peut
alors être traité à l¹aide de méthodes linéaires pour obtenir les données de
chronométrage.
A new technique for
transmission system planning
By G. J. Berg, MIEEE,
MCSEE, K. R.
C. Mamandur, SIEEE, and P. Subramaniam,
Department of Electrical
Engineering, The University of Ca/gary.
Pages: 35-40
This
paper presents an efficient method for solving long-range transmission planning
problems. Minimizing the present worth of investment required for additional
transmission facilities is the main aim of the proposed algorithm. Further, the
method identifies a number of alternative expansion plans in the same computer
run.
A
technique which determines Œshortest paths¹ between nodes in a network is made
use of to identify the suitable right of ways for new transmission lines, and
to determine alternative feasible states of the system. D.C. load flow and an
efficient method of simulating network modifications and outages have been
incorporated.
The
proposed method has been tested on a utility system. Results are presented and
discussed.
Ce texte
présente une méthode efficace pour résoudre les problèmes de transmission à
longue distance. L¹objectif principal de l¹algorithme proposé est de réduire au
minimum la valeur de l¹investissement requis pour des installations
supplémentaires de transmission. De plus, la méthode indique un certain nombre
de plans alternatifs d¹expansion dans la même phase de traitement.
On y
utilise une technique déterminant les ŒŒchemins les plus courts¹¹ entre les
noeuds dans un réseau afin d¹identifier les droits de passage appropriés pour
les nouvelles lignes de transmission et de déterminer des états alternatifs du
système qui soient praticables.
On y a
incorporé la charge à courant continu de même qu¹une méthode efficace de
simuler les modifications et les pannes du réseau.
La méthode
proposée a été mise à l¹essai et ce texte en présente les résultats et
l¹analyse.
1978
– Volume 3 – Numéro 4
Data
communications networks
By C. I. McGibbon, P.
Eng., The Computer Communications Group, TransCanada Telephone System, Ottawa.
Pages:
3-8
This
paper addresses the development of Canada¹s data communications networks in the
context of the development of Canada¹s resources for all Canadians.
Communications provide a means to conserve and/or make more effective use of
other valuable Canadian resources. Also these networks are resources
themselves. These aspects are discussed with particular reference to TCTS¹s
most recent data network, Datapac, a commercial packet-switched network.
Ce texte traite du développement des réseaux
canadiens de communications des données, dans le cadre du développement du
Canada. Les communications fournissent un moyen de préserver et/ou de faire un
meilleur usage d¹autres précieuses ressources canadiennes. Tous ces réseaux
sont des ressources en eux-mêmes. Ces aspects sont présentés en les liant tout
particulièrement au plus récent réseau de données de TCT, Datapac, un réseau
automatique à commutation par paquets.
Net energy analysis of electrical transmission
lines
By D. Mau, Department of Environmental Engineering,
University of Florida,
Suzanne Bayley, Coastal Zone Unit, Department of
Natural Resources, State of Maryland, and
J. Zucchetto, Regional
Science Department, University of Pennsylvania.
Pages: 9-13
This
paper presents an analysis of the energy costs inherent in the construction and
operation of a 1000-mile length of 765 KV AC, ± 400KV DC and ± 600 KV DC
transmission lines. Calculations were made for the indirect energy costs
associated with materials and construction as well as line losses during
operation. Environmental losses were evaluated as energy costs by calculating
the photosynthetic production losses and converting these energy losses to
equivalent coal or electrical units through appropriate conversion factors. In
this way all energy costs could be equally compared. By considering the
electricity transmitted as equivalent to a certain amount of coal, and by
expressing costs in coal units, yield ratios (energy transmitted per unit of
energy cost) were calculated. These turned out to be 9.6 for the 765 KV AC, 8
for the ± 400 KV DC, and 11.9 for the ± 600 KV DC line.
Ce texte présente une analyse des coûts
énergétiques inhérents à la construction et à l¹opération de lignes de
transmission de 765 KV CA, ± 400KV CC et ± 600KV CC, d¹une longueur de 1000
milles. Les calculs effectués comprennent les coûts énergétiques indirects
correspondant aux matériaux et à la construction, de même qu¹aux pertes
d¹énergie subies pendant l¹opération. Les pertes d¹environnement furent
évaluées en termes de coûts énergétiques, en calculant les pertes de production
photosynthétique, et en convertissant ces pertes d¹énergie en des unités
électriques ou calorifiques équivalentes, selon des facteurs de conversion
appropriés. De cette façon, tous les coûts énergétiques peuvent être comparés
également. En considérant l¹électricité transmise comme étant équivalente à une
certaine quantité de charbon, et en exprimant les coûts en unités calorifiques,
il a été possible de calculer des taux de rendement (quantité d¹énergie
transmise par unité de coût en énergie). Ces taux furent de 9.6 pour la ligne
de 765 KV CA, de 8 pour la ± 400 KV CC et de 11.9 pour celle de ± 600KV CC.
TWT noise suppression due to the presence of a
large saturating carrier
By Chun Loo, MIEEE,
Department of Communications, Communications Research Centre, Ottawa.
Pages: 14-16
Input
noise to a traveling wave tube (TWT) is suppressed due to the presence of a
large saturating carrier. This paper describes a method of calculation and
shows that the relationship between output carrier-to-noise ratio (dB) and
input carrier-to-noise ratio (dB) is linear. These results compare well with
experimental values obtained using the CTS/Hermes satellite3.
Furthermore, the calculations show that the amount of suppression of small
signals and noise due to the presence of a large carrier is nearly identical.
Le bruit d¹entrée dans un tube à ondes
progressives (TWT) est supprimé, grâce à la présence d¹un grand transporteur à
saturation. Ce texte présente une méthode de calcul et démontre que le rapport
entre le taux bruit/transporteur à la sortie (dB) elle taux bruit/transporteur
à l¹entrée (dB) est linéaire. Ces résultats sont confirmés par les valeurs
expérimentales obtenues à l¹aide du satellite CTS/Hermes3. De plus,
les calculs démontrent que la quantité de petits signaux et de bruit supprimés,
due à la présence d¹un grand transporteur, est presque identique.
Forecasting peak system load using hybrid models
By N. 0. Uri Oil and Gas Analysis
Division, Office of Energy Source Analysis, Department of Energy, Washington,
D.C.
Pages: 17-23
Realizing
that Box-Jenkins time series analysis lacks any basis in economic theory but at
the same time wanting to take advantage of the excellent forecasting accuracy
of the approach, the first part of this paper takes the basic Box-Jenkins
structure and integrates it into an econometric system. Relating Box-Jenkins
parameters to economic and weather variables allows one so forecast these
parameters. The forecast parameters are in turn used in a Box-jenkins model to
provide a forecast of the series of interest. The result, for a specific
example, proves to be clearly superior to a pure Box-Jenkins model.
An
alternate approach is suggested whereby an econometric model is estimated, the
residual errors analyzed and forecast using a Box-Jenkins time series model,
and then the results of both these models combined. The result, for the same
example, proves to be an improvement over a simple Box-Jenkins model or the
econometric model.
When
the two hybrid models are compared, the first model is the best, judged on forecasting
accuracy. An important feature to consider when using the approaches, however,
is the ease of use. On this basis, the alternate approach is best.
Ce texte, considérant que la méthode d¹analyse
par séries chronologiques Box-Jenkins ne possède aucun fondement en théorie
économique, mais tout en voulant mettre à profit l¹excellente précision des
prévisions de cette méthode, présente, dans un premier temps, l¹intégration
dans un système économétrique de la structure fondamentale de la méthode Box-Jenkins.
Relier les paramètres Box-Jenkins aux variables économiques et météorologiques
permet de prévoir ces paramètres. Les paramètres ainsi calculés sont ensuite
utilisés dans un modèle Box-Jenkins afin de prévoir la série que l¹on cherche à
examiner. Le résultat, obtenu pour un exemple particulier, est clairement
supérieur à celui fourni par un modèle pur de la méthode Box-Jenkins
Le texte présente une méthode différente, selon
laquelle un modèle économétrique est calculé. Les erreurs résiduelles analysées
et prévues selon la méthode d¹analyse par séries chronologiques Box-Jenkins, et
les résultats de ces deux modèles, sont combinés. Le résultat, et les résultats
de ces deux modèles, sont combinés. Le résultat, pour le même cas, est
supérieur à ceux fournis par le modèle simple Box-Jenkins ou le modèle
économétrique.
Si l¹on compare les deux modèles hybrides, le
premier est supérieur au niveau de la précision des prévisions. Cependant, il
est important, dans l¹utilisation de ces méthodes, de considérer la facilité
d¹usage. Sur cette base, la deuxième méthode est plus avantageuse.
The effect of 60 Hz current flow on the heart
By 0. Z. Roy, MIEEE, G. Park, and J. Scott, National
Research Council of Canada, Ottawa.
Pages: 24-28
This
paper describes the effects of 60 Hz current flow and the aspects under which
this current flow can create a problem, particularly in the hospital
environment. The evolution of new surgical and diagnostic procedures has made
it mandatory for the clinician and the clinical engineer to be well acquainted
with the problem. This particularly applies to the clinical engineer who is
charged with the responsibility of electrical hazard control and equipment
maintenance in the hospital.
Ce mémoire s¹intéresse aux effets du courant
60Hz et aux dangers qu¹il peut présenter en milieu hospitalier. L¹évolution des
méthodes de diagnostic et de chirurgie oblige maintenant le clinicien et le
technicien de clinique à bien connaître tous les aspects de cette question. Cette
nécessité s¹applique en particulier au technicien de clinique chargé de la
lutte contre les dangers électriques et de l¹entretien de l¹équipement dans les
hôpitaux.
Etude expérimentale du champ
électrostatique dans les postes et sous les lignes de transport haute
tension
Par M. DeVizio, MICI, et P.S. Manuvada, IEEE
Senior Member.
Pages: 29-32
Dans le but d¹établir un guide général pour l¹évaluation
de l¹intensité du champ électrostatique alternatif dans les postes haute
tension, l¹HydroQuébec a effectué divers relevés dans des postes typiques
et sous quelques lignes de transport haute tension. Le rapport analyse les
intensités de champ électrostatique au voisinage immédiat du sol, telles que
mesurées et calculées. On y trouve aussi des mesures de courants alternatifs
induits dans les personnes placées soit au niveau du sol, soit en position
élevée.
With a view to establishing general guidelines
for evaluating the intensity of alternate electrostatic fields in high-tension
power stations, Hydro-Québec has assembled data in several typical stations and
underneath some high tension transmission lines. The report analyses
electrostatic field intensities at ground level, as measured and as calculated.
Measurements of alternate currents induced in persons at ground level and in an
elevated position are also shown.
A two-wire teleconferencing terminal
By G. W. Holbrook, MCSEE,
MIEEE, and A. Hastings-James, MIEEE, Nova Scotia Technical College.
Pages: 33-37
Based
upon the studies implemented by the Department of Communications, a two-wire
teleconference desk set is proposed employing conventional moving-coil
loudspeakers as bi-lateral transducers. The low electro-acoustic efficiency of
these transducers is significantly increased by the use of a balanced positive
feedback arrangement. Four moving-coil loudspeakers are interconnected with a
conventional two-wire to four-wire termination to produce an overall terminal
which is genuinely two-wire in operation.
The
resulting prototypes produce acceptable levels for both sending and receiving
in an office-to-office situation and can be connected in a multi-party mode.
This eliminates many of the undesirable features of the currently available
voice-switched loudspeaking telephone sets.
Sur la base des études faites par le Ministère
des Communications, on propose un appareil de téléconférence de table à deux
fils, qui utiliserait des haut-parleurs conventionnels à bobines mobiles en
guise de transducteurs bilatéraux. La basse efficacité électroacoustique de ces
transducteurs est nettement augmenté par l¹utilisation d¹un système à
rétroaction positive équilibrée. Quatre haut-parleurs à bobines mobiles sont
reliés à une borne conventionnelle de deux à quatre fils, pour créer une borne
globale qui soit à fonctionnement deux fils véritable. Les prototypes donnent
des niveaux acceptables de transmission et de réception dans une situation de
bureau à bureau, et peuvent être reliés en mode de communication multiple. Ce
système élimine beaucoup des caractéristiques indésirables des appareils
téléphoniques courants à haut-parleurs à commutation vocale.
Étude sur les transformateurs
d¹intensité (Tl) pour le réseau de la Baie-James
Par L. Masson, MIEEE,
Direction Puissance, Institut de recherche de l¹Hydro-Québec, Varennes, Québec.
Pages: 38-40
Dans le cadre d¹une étude compréhensive par
Hydro-Québec des principes et systèmes de protection pour le projet de 735-KV
de la Baie lames, une enquête spéciale a été menée sur les transformateurs de
courant à utiliser, en vue d¹améliorer le choix et les caractéristiques de ces
dispositifs. Après une étude des noyaux de transformateurs à écartement et
fermés, on a fait des calculs pour identifier le meilleur compromis entre les
dimensions des noyaux et la précision des transformateurs de courant, dans les
conditions suivantes:
Courant primaire nominal: 4000
A efficace
Courant de court-circuit: 50
KA efficace
Constante de temps de l¹élément
à conductibilité unilatérale 150
ms
Temps de coupure de saturation 175 ms
Coupure-coupure: 100
ms, 500 ms, 60 ms
Charge: 26VA,
cos Ф 0,9
La solution optimale pour une précision de 5%, s
été reconnue comme étant un transformateur de courant à écartement avec un
rapport de 4000/1 et un facteur de surdimensionnement d¹environ 40.
Within the framework of a comprehensive study
by Hydro-Quebec on the principles and systems of protection for the 735-ky
James Bay project, a special investigation was undertaken into the current
transformers to be used with a view to optimizing the choice and
characteristics of these devices. Following a study on gapped and gapless
current transformer cores, calculations were performed to determine the best
compromise between the dimensioning of the cores and the accuracy of the
current transformers, for the following system conditions:
Nominal
primary current: 4000
A rms
Short-circuit
current: 50
kA rms
Time
constant of asymmetrical component: 150
ms
Time
to saturation CO: 175
ms
CO-CO: 100
ms 500 ms 60 ms
Burden: 26
VA, cos Ф = .9
The optimum solution for a 5% accuracy has been
found to consist of a gapped current transformer having a ratio of 4000/1 and
an overdimensioning factor of about 40.